    SIZING CONDENSER TO EVAPORATOR

    [siteorigin_widget class=”WP_Widget_Media_Image”][/siteorigin_widget] MANY TIMES WE GET THE QUESTIONS, “HOW DO YOU SIZE THE CONDENSER WITH YOUR EVAPORATOR?”. HERE ARE SOME HELPFUL GUIDELINES WHEN SIZING.   SELECT CONDENSING UNIT WITH A LOWER CAPACITY THAN THE EVAPORATOR    ( 90% to 100% OF EVAPORATOR ) DESIGN POINT – 38° SST (USE 40°F FOR SIZING PURPOSES) IF RUNNING ROOM AT 55°  GOLDILOCKS TYPE OF CONDITIONS USE A GOOD AVERAGE TEMPERATURE  NOT WORST CASE SCENARIO    ON HOT DAYS JUST LET THE SYSTEM RUN A LITTLE LONGER FOR THE OUT OF BOUNDS CONDITIONS ROOMS ARE SIZED FOR 16 HOUR RUN DAY LOAD ON EVAPORATOR IS CONSTANT- ITS THE CONDENSING UNIT THAT NEEDS TO RUN A…